Bentec circuit breakers have been designed to meet
stringent
conditions which meet salient specifications IS;8828
IEC Pub
898(95). Bentec MCB is a high fault capacity thermal
magnetic
type of breaker, which protects against overload
and short
circuits . Overload protection is achieved with
a thermal
bimetal strip, which gets heated in case of overload
that in
turn pushes the trip latch, which releases the contacts.
In case
of short circuits, the high fault current energizes
the magnetic
coil resulting in plunger striking the trip lever,
which
ensures immediate release of the breaking mechanism.
Features:
1. Meets latest standards
2. Current limiting design
3. Fire retardant body
4. Energy saving
5. Clause 9.6 of 8828
6. Shock proof: Finger Proof as per test
7. Quick Break Operating Mechanism
8. 12 plate Arc chute
9. Angular Vents
10. Din Rail mounting (35mm Din Rail)
11. Pad covering in ON/OFF position
|
|
|
|
| |
Specifications
Number of Poles
Rated Current(In)
Rated Voltage (Ue)
Tripping Characteristics
Rated Breaking Capacity (Icn)
Rated Frequencies
Housing
Insulation Voltage( Ui)
Type of Terminals & Maximum
Cable Cross section
Impulse power frequency Voltage
Impulse withstand Voltage (Uimp)
Degree of Protection
Mounting
Ambient temperature |
|
IS
8828: 1990, IEC Pub 898 (1995)
1, 1 + N, 2, 3, 3 + N and 4
0.5 to 62
240/415 VAC and 220 VDC
B and C characteristic
6/10 KA
50/60 Hz
Polybutylene Terephalate
500V
25mm Box Type terminals on the incoming &
25mm Block Type terminal on the outgoing
3 KV (50/60
Hz)
5 KV (1.2/50 micro sec)
IP 20
Clip Mounting Rails, 35 mm
Tmax=55 degree C Tmin= -25 degree C
|
|
|
|
|
|
|