Bentec circuit breakers have been designed to meet stringent
conditions which meet salient specifications IS;8828 IEC Pub
898(95). Bentec MCB is a high fault capacity thermal magnetic
type of breaker, which protects against overload and short
circuits . Overload protection is achieved with a thermal
bimetal strip, which gets heated in case of overload that in
turn pushes the trip latch, which releases the contacts. In case
of short circuits, the high fault current energizes the magnetic
coil resulting in plunger striking the trip lever, which
ensures immediate release of the breaking mechanism.



Features:

1. Meets latest standards

2. Current limiting design

3. Fire retardant body

4. Energy saving

5. Clause 9.6 of 8828

6. Shock proof: Finger Proof as per test

7. Quick Break Operating Mechanism

8. 12 plate Arc chute

9. Angular Vents

10. Din Rail mounting (35mm Din Rail)

11. Pad covering in ON/OFF position


   
 
Specifications


Number of Poles


Rated Current(In)


Rated Voltage (Ue)


Tripping Characteristics



Rated Breaking Capacity (Icn)


Rated Frequencies


Housing


Insulation Voltage( Ui)



Type of Terminals & Maximum
Cable Cross section


Impulse power frequency Voltage


Impulse withstand Voltage (Uimp)


Degree of Protection


Mounting


Ambient temperature


IS 8828: 1990, IEC Pub 898 (1995)


1, 1 + N, 2, 3, 3 + N and 4


0.5 to 62


240/415 VAC and 220 VDC


B and C characteristic



6/10 KA


50/60 Hz


Polybutylene Terephalate


500V



25mm Box Type terminals on the incoming &
25mm Block Type terminal on the outgoing

3 KV (50/60 Hz)


5 KV (1.2/50 micro sec)


IP 20


Clip Mounting Rails, 35 mm


Tmax=55 degree C Tmin= -25 degree C